1.8 Control Terminals

30A 30C 30B AXA AXC
Type
Symbol
P1, P2, P3
FX
RX
JOG
BX
RST
CM
NC
VR
V1
I
5G
FM
30A
30C
30B
AXA, AXC
Comm.
CN3
All manuals and user guides at all-guides.com
Name
Multi-Function input
Used for Multi-Function Input Terminal.
1, 2, 3
(Factory default is set to "Step Frequency 1, 2, 3".)
Forward Run Command
Forward Run When Closed and Stopped When Open.
Reverse Run Command
Reverse Run When Closed and Stopped When Open.
Jog Frequency
Runs at Jog Frequency when the Jog Signal is ON. The Direction is set by
Reference
the FX (or RX) Signal.
When the BX Signal is ON the Output of the Inverter is Turned Off. When
Motor uses an Electrical Brake to Stop, BX is used to Turn Off the Output
Emergency Stop
Signal. When BX Signal is OFF (Not Turned Off by Latching) and FX Signal
(or RX Signal) is ON, Motor continues to Run.
!
Fault Reset
Used for Fault Reset.
Sequence Common
Common Terminal for Contact Inputs.
-
Not Used.
Frequency Setting Power
Used as Power for Analog Frequency Setting. Maximum Output is +12V,
(+10V)
100mA.
Frequency Reference
Used for 0-10V Input Frequency Reference. Input Resistance is 20 KΩ
(Voltage)
Used for 4-20mA Input Frequency Reference. Input Resistance is 250 Ω
Frequency Reference
(Current)
Frequency Setting
Common Terminal for Analog Frequency Reference Signal and FM (For
Common Terminal
Monitoring).
Outputs One of the Following: Output Frequency, Output Current, Output
PWM Output
Voltage, DC Link Voltage. Default is set to Output Frequency. Maximum
(For External Monitoring)
Output Voltage and Output Current are 0-12V and 1mA. Output Frequency
is Set at 500Hz.
Activates when Protective Function is Operating. AC250V, 1A or less;
DC30V, 1A or less.
Fault Contact Output
Fault: 30A-30C Closed (30B-30C Open)
Normal: 30B-30C Closed (30A-30C Open)
Multi-Function Output
Use after Defining Multi-Function Output Terminal. AC250V, 1A or less;
Relay
DC30V, 1A or less.
Communication Port
Keypad Connection Port.
P1
P2
P3
FX RX NC VR
JOG CM CM BX RST
Description
13
Chapter 1 - Installation
V1
I
FM 5G