Wiring Control Terminals

Wiring Precautions
CM and 5G terminals are insulated to each other. Do not connect these terminals with each other and do
not connect these terminals to the power ground.
Use shielded wires or twisted wires for control circuit wiring, and separate these wires from the main
power circuits and other high voltage circuits.
Use 1.25mm²(22AWG) stranded cables for control terminal connection.
Control Circuit Terminal
The control input terminal of the control circuit is ON when the circuit is configured to the current flows out of
the terminal, as shown in the following illustration. CM terminal is the common terminal for the contact input
signals.
External Sequence
Do not apply voltage to any control input terminals (FX, RX, P1, P2, P3, JOG, BX, RST, CM).
All manuals and user guides at all-guides.com
Resistor
Current
FX
Resistor
RX
CM
Inverter Circuitry
!
CAUTION
14
Chapter 1 - Installation
24 VDC