Application parameters

Parameters Description, values, default value
SPx
Switch Point (for switching outputs 1/2)
Value at which the output changes its switching status.
SP1 = switch point output 1 (slip/synchronous monitoring)
SP2 = switch point output 2 (monitoring of the rotational speed of the drive)
The outputs switch independent of each other.
• Values SP1: 0.1...99.9% (slip)
• Values SP2: 1...1000.0 Hz or 1...60,000 RPM (Note parameter DIM!)
• Default value:
HYx
Hysteresis (for switching outputs 1/2)
The hysteresis value determines the distance of the reset point to the switch point SPx and
prevents a possible chattering of the corresponding switching output.
In connection with switching functions 5 and 6 (FOx) an acceptable range or an error range
can be defined for output 2. (Not useful for output 1.)
The window range in which the hysteresis is effective in both directions is set by means
of a "ficticious" switch point SP.
SP
max
SP =
SP – SP
HY =
• Values: 0.0...1000.0 % of the value for SPx
• Default values: HY1 = 10.0 / HY2 = 5.0
STx
Start-Up Delay (for switching outputs 1/2)
This function is used as time-dependent start-up delay and serves for suppressing error
messages during start-up of the plant.
After switching on the unit or after removal of the 24 V signal the corresponding output is
maintained in the "good" state for the time set.
• Values: 0.0...1000.0 s
• Default value: 0.0 (no start-up delay)
DTx
Delay Time (for outputs 1/2)
Enables delayed switching of outputs 1/2.
The corresponding output switches only if the current value is above or below the switch
point for more than the time set here.
• Values: 0.0...1000.0 s
• Default value: 0.0 (no delay time)
FTx
Fleeting Time (for switching outputs 1/2)
If the current value is above or below the set switch point, the output changes its state
during the set time and then switches back to the initial state (irrespective of the switching
event still being active or not).
• Values: 0.0...1000.0 s
• Default value: 0.0 (fleeting time not active)
All manuals and user guides at all-guides.com
SP1 = 5 [%], SP2 = 500 [RPM]
+ SP
min
2
min
x 100 [%]
SP
FS-1 / FS-1N
MONITOR
f
FOx = 5/6
SP
max
HY
SP
HY
SP
min
t
31