6. Adjustable parameters

Parameter
P00 keyboard locking
operating mode:
- level of the input signal and
P01
- display mode proportional
scaling factor:
P02
numerical value to be displayed with the
maximum of the input signal
P07 decimal point of the display
preset 1 (minimum value):
P10
displayed value at which OUT 1 (min.)
is to switch
preset 2 (max.):
P11
displayed value at which OUT 2 (max.)
is to switch
switching performance of the outputs
P12
OUT 1 (min.) and OUT 2 (max.)
offset
P17
numerical value which is added to the
current displayed value
linearisation
P16
free definition of a linearisation graph for
the displayed values
fleeting time for OUT 1 (min.)
The output changes its switching status when
P18
the limit value has been exceeded or has not
been reached for the length of the set fleet-
ing time. Then it returns to the initial status.
P19 fleeting time for OUT 2 (max.)
P20 fleeting time for OUT 3 (display 0)
P23 function of the
mode
P24 function of the
mode
P25 function of the
mode
P26 read min./max. memory
P27 read max./min. memory
start-up delay for OUT 1 (min.)
The output switches after the start-up delay
P29
has elapsed.The time starts with the applica-
tion of the operating voltage or after reset.
14
reciprocal
key in the operating
key in the operating
key in the operating
Parameter value
0 = keyboard locking inactive
1 = keyboard locking active
1 = 0 ... 1 V; 0 ... xx V / proportional display
2 = 0 ... 10 V / proportional display
3 = 0 ... 20 mA / proportional display
4 = 4 ... 20 mA / proportional display
5 = 0 ... 1 V; 0 ... xx V / reciprocal display
6 = 0 ... 10 V / reciprocal display
7 = 0 ... 20 mA / reciprocal display
8 = 4 ... 20 mA / reciprocal display
range of values: 1 ... 999 999
range of values: 0 ... 5
0 = none, 5 = 5 places after the point
range of values: 0 ... 999 999
range of values: 0 ... 999 999
1 = both outputs switch when the relevant preset
value has been exceeded
2 = output (min.) switches when the relevant
preset value has not been reached, output
(max.) switches when the relevant preset value
has been exceeded
range of values: -99999 ... +99999
0 = linearisation inactive
1 = linearisation active
range of values: 0.00 ... 9.99s
(0.00 = fleeting time not active, output is switched
statically)
range of values: 0.00 ... 9.99s; (0,00: see P18)
range of values: 0.00 ... 9.99s; (0.00: see P18)
0 = no function
5 = delete min./max. memory
0 = no function
5 = delete min./max. memory
0 = no function
5 = delete min./max. memory
display of the current minimum value
display of the current maximum value
range of values:
0s = start-up delay not active
0.01 ... 99.98s start-up delay active
99.99s = output "min." remains locked until the
displayed value falls below the preset min. value
for the first time