Herunterladen Inhalt Inhalt Diese Seite drucken

Operating And Indicating Elements - IFM Electronic ecomat 200 FS-1 Betriebsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

FS-1 / FS-1N
MONITOR

3. Operating and indicating elements

1
7
MONITOR FS-1N
Frequency/Slip
In 1
4
In 2
Err
6
13
19
1 Display (7/14-segment)
1a Indicators for input channels and operating modes:
CH1...CH4
RUN
PRG
TST
KEY
1b Indication:
1c Indication:
2 Push buttons
/ : Selection of the actual value display, parameter selection,
3 Push button
:
4 LEDs In1/2 (yellow): Input pulses
LED Err (red):
5 LEDs Out1/2 (green): Switching status of the outputs 1 and 2
Off:
On:
Quickly flashing:
Slowly flashing:
6 Panel for labelling
24
PAGE
All manuals and user guides at all-guides.com
2
3
4
5
6
8
9
10
11
12
Out1
Out2
14
15
16
17
18
20
21
22
23
24
Input channels (here: CH1 and CH2)
Run mode (normal operating mode)
Programming mode (setting of the parameter values)
Test function (offline check of the switching characteristics)
Status of the unit (locking)
Actual values and parameter values (5-digit, numerical)
slip: 0.1...99.9%, rotational speed: 0...60,000 RPM,
pulses: 0.1...1000.0 Hz
Outside the value ranges the display shows "----".
Parameter abbreviation and units (3-digit, alphanumeric)
setting of the parameter values
Selection of the operating mode,
acknowledgement of the parameter value, front reset
(only FS-1N) lights in case of wire break or short circuit on the cable of the
pulse pick-up, at the same time the CH indicator of the faulty input flashes
The output is not switched (relay de-energised, transistor blocked)
The output is switched (relay energised, transistor switched)
The output is kept latched (parameter SOx, Store Output)
The delay time is effective for the output. The output switches when the
delay time has elapsed and the trigger event is still present
(parameter DTx, Delay Time)