Herunterladen Inhalt Inhalt Diese Seite drucken

Commissioning; Operation - Bwt Multipur M Einbau- Und Bedienungsanleitung

Dn 65 – dn 150 rückspülfilter, manuell
Inhaltsverzeichnis
Verfügbare Sprachen

Verfügbare Sprachen

EN
26
7

Commissioning

Check the filter and rinsing water line for correct
installation and leakage.
Turn handwheel (1) clockwise until the stop is
reached to carry out a first backwashing.
Close the flushing water outlet.
Open the on-site shut-off valves upstream and
downstream from the backwash filter.
1
Vent the pipeline via the next connection after the
filter.
The filter is ready for operation.
2
8

Operation

The filter must be backwashed at the latest when
the max. permissible pressure difference (1.2 bar)
is reached.
We recommend backwashing the filter at least
3
once a month.
Turn the handwheel (1) counterclockwise to the
upper stop. Close the filter by turning it clockwise.
5
Set the date for the next backwash on the date
ring (4).
4
6
7

Kapitel

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Multipur m 65Multipur m 80Multipur m 100

Inhaltsverzeichnis