Herunterladen Inhalt Inhalt Diese Seite drucken

Zehnder Pumpen Kompaktboy Doppel Gebrauchsanleitung Seite 79

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

described in the following. Mounting of the right valve is carried out analogously.
Kompaktboy Double
1.
2.
Insert the threaded bolt (M16x80) into hole 1 of
the valve and secure it on the valve side with
one nut (M16) each.
3.
congruently.
4.
Screw the nut (M16) on the threaded bolt from
below.
5.
Screw in the 3 screws M16x60 and
tighten the 4 screw connections equally cross-
wise.
6.
Put the flange seals DN 100 on the connection
flanges of the shut-off valves.
7.
Put on the Y-pipe. While doing so, arrange the
holes/threaded holes congruently.
8.
Create the screw connections with 4 screws
M16x90 and 4 nuts M16 between the shut-off
valves and the Y-pipe and equally tighten cross-
wise.
9.
Create the screw connections with 4 screws
M16x100 and 4 nuts M16 between the Y-pipe
and the adapter flange and equally tighten
crosswise.