Herunterladen Inhalt Inhalt Diese Seite drucken

Preventive Maintenance; Residual Current Devices; Only For Column With Restart - Gewiss JOINON I-ON Serie Installations- Und Bedienungsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 173

Preventive maintenance

15. Preventive maintenance

15.1. Residual current devices

The residual current circuit breaker must be tested using the relative test button key at least once every 6 months.
Keep a record that the test was carried out correctly, following the current rules.
The front door must only be opened to carry out the test on both residual current devices, avoiding contact with any
other accessible device or cable.
The operator who accesses the protection devices must have received suitable training from the contractor
(charging station operator), and be authorised to perform these operations.

15.2. Only for column with Restart

The residual current circuit breaker must be tested at least every 6 months, as shown below. Keep a record that the test
was carried out correctly, following the current rules.
1
7.55.4.515.2 - Installation and Operation Manual
Installation and Operation Manual
3A
3B
2
Gewiss
CLACK
85
IT
EN
FR
ES
DE
RO
HU
NL

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Joinon i-on wall serie

Inhaltsverzeichnis