effeff 1338-14 Installations- Und Montageanleitung Seite 48

Vorschau ausblenden Andere Handbücher für 1338-14:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Tab. 2
DIP switch S4
(Fig. 5)
top switch: ON
bottom switch: OFF
EN
48
Mode 1: Stand-alone operation –
Mode 2: Bus operation –
DIP switch S4
Function
1
ON
Door opening time monitoring active with alarm.
factory
default
OFF
No pre-alarm or alarm due to door opening time monitoring
2
ON
Temporary release is possible with the internal key pushbut-
factory
ton, via terminal 20 or via the external push-button.
default
OFF
Temporary release is only possible by the external push-but-
ton connected to terminals 11/12.
3
ON
Permanent release takes place immediately after actuation
factory
default
OFF
Permanent release only takes place after 5 seconds of contin-
uous actuation.
4
ON
An acoustic alarm is emitted when the external fire alarm
factory
system is triggered.
default
OFF
No acoustic alarm is emitted after the external fire alarm
system is triggered
5
ON
Mode 2 –
OFF
Mode 1 –
factory
default
models 1338-14 and 1338-20
The escape door control terminal operates as
a bus participant on the door control bus.
Models 1338-20
Escape door control terminal operates as a
stand-alone unit.
Models 1338-14 and 1338-20
model 1338-20
Configuration