Verfügbare Sprachen

Technical Data
Power Consumption Total System
Basic System without External
Consumer
System with External Consumers
Mechanics and connectors
Protection type acc. IEC 60529
Protection class acc. IEC 61140
Power Supply (PS-8630)
DC voltage input
Input voltage
Input power
Protection type
Rated impulse voltage
System voltage outputs
Output voltages
System internal
System external
External I/Os
Contact wetting
Modem supply (via X2)
1)
not short-circuit proof and not overload proof
2)
Protective mechanism is a self resetting fuse (PTC)
Parameter:
Operation voltage: DC 60 Vmax
Switching capacity: < 40 A
Ohmic resistance: < 5 Ohm
Permanent floating current after activation of the fuse: < 1,3 A

Communication interfaces

Rated impulse voltage
Ethernet/LAN
X1, X4
serial RS-232
X2
serial RS-485
X3
Binary inputs (DI-8100)
12 binary inputs
Nominal voltages
Max. operating voltage
Rated current
Dynamic suppression of noise
caused by cable capacitance
Terminals
Rated impulse voltage
Binary outputs (DO-8203)
8 binary outputs (relay)
Nominal voltage
Maximum continuous current
Circuitry with derating
CP-8000 Product Information
C53207-A520-C6-5A-7483 / DC8-002-2.04; Edition 03.2017
4,3 W
If a basic system is expanded with external
consumers (modem, I/O modules) then you have
to add their power consumption to that of the
basic system.
Please note, that the power consumption values
of the external consumers must be adjusted
because of the efficiency factor of the internal
power supply PS-8630 (typical 80 %; sub-zero
temperature 77 %).
IP 20 / IP 40 Housing front
2
DC 24 to 60 V
+ 15 % / - 25 % *)
+ 30 % / - 25 % **)
*) caused by the connection between input
voltage and AUX V0 the input voltage must be
< DC 70 V
**) the reliable function of the power supply is
guaranteed up to DC 78 V
34 W
double insulation
4 kV (category III / AC 230 V)
DC 5,2 V
± 3 %
2,5 W
DC 12 V
+ 30 / - 5 %
3 W
1)
DC 5,2 V
± 3 %
2,5 W
equals input voltage
3x each 100 mA
de-energized (for modem reset)
DC 5,2 V
± 5 %
2,5 W
DC 12 V
± 5 %
2,5 W
2 kV
- RJ45-connector 8-pole (IEC 60603-7)
- Auto-MDI(X)
- galvanically insulated
- D-SUB 9-pole, male (DIN 41652)
- not galvanically insulated
- Line length < 2.5 m (cabinet internal)
- Screw terminal 6-pole
- galvanically insulated
2 groups (with 8 and with 4 inputs)
DC 24/48/60 V
DC 78 V
0,6 to 1,5 mA (at DC 18 to 78 V)
typ. 220 nF (for DC 18 to 78 V)
Removable screw terminals (grid size 5.08)
4 kV (category III / AC 230 V)
4 groups with 2 outputs each
DC 24/48/60/110/220 V
AC 110/230 V
3 A (5 A/1 min)
see document: SICAM I/O Modules
Switching capacity - DC voltage
Switching capacity - AC voltage
Switching cycles
Output circuits
Rated impulse voltage
Terminals
Climatic ambient conditions
Operation temperature
Temperature gradient
Relative air humidity
Air pressure
Temperature for storage/transport
Pollution degree
2)
SICAM A8000 Series
CP-8000 Master Module with I/O
min. 50 mW at DC 5 V
max. acc. to diagram
max. 1250 VA; 5 A / AC 250 V, resistive load
max. 500 VA; 2 A / AC 250 V, cosϕ = 0.4
4
3x10
Max. DC 250 V / AC 253 V (operated by means
of an external voltage)
4 kV (category III / AC 230 V)
Removable screw terminals (grid size 5.08)
- 40 to + 70 °C
≤ 30 °C/h
5 to 95 % (condensation not permissible)
70 to 106 kPa (up to 3000 m)
- 30 to + 85 °C
2