Point
Instel.
[-]
[%]
1
30
2
34
3
40
4
46
5
49
6
53
7
56
8
57
9
64
10
69
11
74
12*
83
13*
91
14*
95
- * Only for the ComfoAir Standard 375
- Sound power reference level is 1pW.
- Sound pressure reference level is 20 μPa.
- Sound power levels measured according to ISO 3741:2010.
- Extract noise measured according ISO 5135:1997 (L w values include end reflection correction (therefore, values
are in duct values)).
- Supply noise measured according ISO 5135:1997 (L w values include end reflection correction (therefore, values
are in duct values)).
- cos phi with preheater turned off (if present)
Qv
P
[m³/h]
[Pa]
[A]
125
13
0,15
125
32
0,18
125
61
0,21
210
29
0,33
210
50
0,38
200
92
0,41
185
131
0,45
263
50
0,52
290
60
0,65
260
151
0,76
240
229
0,85
375
100
1,22
340
258
1,53
300
351
1,53
I
Pe
cos phi
[W]
[-]
16
0,43
19
0,44
24
0,46
39
0,51
45
0,5
49
0,52
55
0,52
64
0,53
81
0,54
95
0,54
108
0,54
156
0,55
196
0,55
197
0,55
Supply
Extract
Casing
dB(A)
dB(A)
dB(A)
49
35
52
39
54
41
59
45
60
46
61
48
64
54
63
53
66
52
68
52
69
56
70
58
73
58
74
59
34
37
40
44
45
47
49
48
51
53
55
58
59
61