2.6. Teach procedure by use of SCTL55 or an IO-Link master

The setpoints can be set-up using a teach procedure, this ensures that the setpoints a set at an optimal value
taking into consideration safe limits and hysteresis.

2.6.1. External Teach (Teach-by-wire)

NB! This function works in Single point Mode, and only for SP1 in SSC1.
The Teach by wire function must be selected first using the SCTL55 or an IO-link master:
a) Select "Teach in" in "Channel 2 (SO2)" -> "Channel 2 Setup.Stage Mode.
b) Select "Single point mode" in "Switching signal channel1" -> "SSC1 Configuration.Mode".
c) Select "Teach by wire" in "SSC1 Single Point" -> "Selection of local/remote adjustment".
Teach-by-wire procedure.
1) Place target in front of sensor.
2) Connect Teach wire input (Pin 2 white wire) to V+ (Pin 1 brown wire).
Yellow led start to flash with 1Hz (10% on), indicating that Teach is running.
3) After 3-6 sec Teach window is open. Here flash pattern changes to 90% on. Release white wire.
4) If Teach is done successfully, yellow led makes 4 flash (2Hz, 50%).
5) The new teached setpoint can be found in "SSC1 Single Point" -> "Setpoint" -> " SSC1 Parameter.Set Point 1".
If Teach fails or is suspended, sensor will exit Teach mode.
NB: If white wire is released outside the Teach window, teach is suspended.
If white wire is not released within 10 sec., teach is suspended (timeout indicated by a number of fast yellow
flash (5Hz, 50%)).

2.6.2. Teach from IO-Link Master or Smart configurator (SCTL55)

1. Select SSC1 or SSC2 configuration mode:
SSC1: Select: "Single point", "Window" or "Two Point" in " Switching signal channel1" ->
"SSC1 Configuration.Mode".
NB! If "Single point" is selected, then "IO-Link adjustment" must be chosen in "SSC1 Single Point" ->
"Selection of local/remote adjustment"
SSC2: Select: "Single point", "Window" or "Two Point" in "Switching signal channel2" ->
"SSC2 Configuration.Mode".
2. Select channel to be taught e.g. "Switching signal channel 1" or "Switching signal channel 2" in
"Teach-in" -> "Teach-in,Select".

2.6.2.1. Single point mode procedure

1) Single value teach command sequence:
Single value teach command sequence.
(Buttons are found in: "Teach-in SSC1" or "Teach-in SSC2" -> "Teach in single value SSC1" or
"Teach-in single value SSC2").
1. Place the target in front of the sensor.
2. Press "Teach SP1".
3. Teach-in result is shown in "Teach-in Result. -> Teach-in State" e.g. "SUCCESS".
4. QoT is shown in "Quality of Teach" e.g. 100%.