Herunterladen Inhalt Inhalt Diese Seite drucken

AERMEC VMF-RCC Handbuch Seite 75

Vorschau ausblenden Andere Handbücher für VMF-RCC:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

Regulation and Control Service
Project
VMF-RCC panel
Subject
Electronic adjustment
E5 panel technical specifications
Document
Edition
1
Date
C
HRONOTHERMOSTAT ENABLING PAGE FOR HEAT PUMP
This page can be used to enable/disable the "chronothermostat" functioning of the E5 panel for
controlling the heat pump or a chiller and select a daily hourly program.
C
HRONOTHERMOSTAT FUNCTION FOR HEAT PUMP
For particular systems such as radiating floors or heating radiators, switch-on/off of the heat
pump can be controlled by management of the chronothermostat implemented in the E5 panel.
This functionality is enabled only if the following condition is satisfied:
There are no fan coils connected to the RS485 network in the system.
The production of domestic hot water in the system is not managed through the
MultiControl system
To access the parameters that specify this functioning, just press the
the conditions listed above), available in the "Chiller" and "Force Off Machine" pages.
R
OOM TEMPERATURE PAGE
This page is used to set the room thermostat's set temperature and the functioning band
implemented by the E5 panel. The admissible values for these parameters are:
 12.5 ÷ 35.0 °C => Machine setpoint
 0 ÷ 2.0 °C
File
09/08/2017
Author
=> On-Off band
SpecificheTecnicheVMF_RCC(Ed0)_EN.doc
F. Carpanese
/
CHILLER
Page 23/61
Code
Group
Code
Type
indoor
key (only visible in
2104_2696105_00
75

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis