Recommended settings:
Nominal battery voltage
12V
24V
36V
48V
60V
120V
144V
288V
3.8 Alarm, buzzer and relay:
On most of the BMV's readings an alarm can be triggered when the value
reaches a set threshold. When the alarm becomes active the buzzer
starts to beep, the backlight flashes and the alarm icon is visible in the
display along with the current value.
The corresponding segment will also flash. AUX when a starter alarm
occurs. MAIN, MID or TEMP for the corresponding alarm.
(When in the setup menu and an alarm occurs, the value causing the
alarm will not be visible.)
An alarm is acknowledged when a button is pressed. However, the alarm
icon is displayed as long as the alarm condition remains.
It is also possible to trigger the relay when an alarm condition occurs.
BMV-700 and -702
The relay contact is open when the coil is de-energised (NO contact), and
will close when the relay is energised.
Factory default setting: the relay is controlled by the state of charge of the
battery bank. The relay will be energised when the state of charge
decreases to less than 50% (the 'discharge floor'), and will be de-
energised when the battery has been recharged to 90% state of charge.
See section 4.2.2.
The relay function can be inverted: de-energised becomes energised and
vice versa. See section 4.2.2.
When the relay is energised, the current drawn by the BMV will increase
slightly: see technical data.
16
Recommended Charged Voltage setting
13.2V
26.4V
39.6V
52.8V
66V
132V
158.4V
316.8V