2.

Operating conditions

Correct use
The unit is a server cabinet cooling device and is only used for the
removal of heat from server cabinets to protect temperature
sensitive components. The cooling system in the cabinet is thermally
independent of the room air. Total heat load of the installed equipment is
taken out of the room using the chilled water circuit. Note: Under special conditions a very
small amount can dissipate to the room (approx. 05, kW)
For reliable function of the CoolTherm, chilled water
must be available in the correct amount, and at the correct
temperature and pressure. Observe water quality as per
VGB-R 455 P. (see Appendix)
Ambient temperature:
Absolute humidity in the installation location:
Water temperature, feed:
Water temperature, return:
Temperature spread, water:
Use of anti-freeze in the chilled water:
Water connection:
Condensed water connection:
Nominal voltage at cooling capacity:
10 KW, 15 KW, 22 KW
Max. operating pressure:
CoolTherm
01.998.330.0 issue / Ausgabe h
10°C / 50°F to 35°C / 95°F
(other temperatures upon request)
Temperatures on use of RMS with
temperature-dependent alarm:
20°C / 68°F to 25°C / 77°F
8 g H
O/ kg air maximum
2
12°C / 53°F
(other temperatures upon request)
18°C / 64.4°F
(other temperatures upon request)
6K
upon request
from below
from below
200V to 264V /
50Hz to 60 Hz
10 bar / 145 PSI
page / Seite 6/76