Chilled Water Connection - Knurr Cooltherm Bedienungsanleitung

Schaltschrank mit integrierter flussigkeitskuhlung nutzkuhlleistung 10 - 22 / 35 kw
Vorschau ausblenden Andere Handbücher für Cooltherm:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

CoolTherm
Manual / Bedienungsanleitung
Remove recirculation air duct transport lock
After positioning remove the transport lock screws at the sides of the recirculation air duct.
The recirculation air duct can be pulled out to remove items which possibly had felt into the head
exchanger tray.
Remove both screws
5.3

Chilled water connection

The heat exchanger can be pulled out for servicing
Chilled water pipes should be connected so that the heat exchanger
can be pulled out when the connection is undone.
If the heat exchanger is connected to the chilled water network using threaded fittings,
the pipe fitting must be supported on tightening.
Prior to commissioning the server cabinet, the pipe connections
should be checked for leaks.
Preparing heat exchanger for initial commissioning:
-
Check the mechanical installation and the supply pipe connection.
CoolTherm
01.998.330.0 issue / Ausgabe h
page / Seite 19/76