CoolTherm
Manual / Bedienungsanleitung
CoolTherm must be installed on a level surface.
For this reason, check the horizontal alignment with a spirit level
prior to starting installation.
Note that the floor must be able to support a rack load of
1.500 kg/m² (with installed equipment per CoolTherm).
To achieve good air circulation, ensure that
there is no packaging material or other equipment that could hinder
or prevent air circulation
5.2

Positioning the units

After positioning, the feet on the CoolTherm are to be set such that the cabinet is vertical. When
positioned the doors must close easily.
The feet are adjusted using a spanner (M 12).
As an option it is possible to connect the cabinets together. There for remove the plugs from the
side panels and connect with hex screw, item no. 4000 1411.
CoolTherm
in the area of the equipment
in the area of the heat exchanger
in the air inlet
in the air outlet
01.998.330.0 issue / Ausgabe h
Distance
feets
W700 D1200
W800 D1200
W800 D1300
Adjustable feets
B1
T1
(mm)
(mm)
600
1114
700
1114
700
1214
page / Seite 18/76