Technical Data - S+S REGELTECHNIK AERASGARD KCO2- W Bedienungs- Und Montageanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

G
®
AERASGARD
KCO2 - SD / KCO2 -W
Patented quality product (patent no. DE 10 2014 010 719.1)
Maintenance-free duct sensor AERASGARD
on lid, for determining the CO2 content of the air (0...2000 ppm/0...5000 ppm). The measuring transducer converts the measured values into a
standard signal of 0 -10 V.
Maintenance-free duct sensor AERASGARD
enclosure with quick-locking screws, optionally with/without display, for determining the CO2 content of the air (0...2000 ppm/0...5000 ppm). The
measuring transducer converts the measured values into a standard signal of 0 -10 V or 4...20 mA (switchable).
The sensor is used in offices, hotels, convention centres, apartments, shops, etc. for the purpose of evaluating the indoor climate. This enables
energy-saving room ventilation on an as-needed basis, thereby reducing operating costs and improving well-being. One sensor for every 30 m²  of
space is recommended.
The CO2 measurement is performed using an optical NDIR sensor (non-dispersive infra-red technology).The detection range is calibrated for
standard applications such as monitoring residential rooms and conference rooms.

TECHNICAL DATA

Power supply:
Power consumption:
Sensor:
Measuring range:
Output:
Relay output:
Measuring accuracy:
Temperature dependence:
Pressure dependence:
Long-term stability:
Gas exchange:
Warm up time:
Ambient temperature:
Response time:
Electrical connection:
Housing:
Housing dimensions:
Cable connection:
Protective tube:
Process connection:
Protection class:
Protection type:
Standards:
Optional:
®
KCO2-SD with active output, automatic calibration (fixed), in a compact plastic enclosure with snap-
®
KCO2-W with active/switching output, automatic calibration (can be deactivated), in a compact plastic
24 V AC ⁄ DC (± 10 %)
< 1.5 W ⁄ 24 V DC typical; < 2.9 VA ⁄ 24 V AC typical; Peak current 200 mA
optical NDIR sensor (non-dispersive infra-red technology),
with manual calibration (via zero button),
KCO2 - SD
with automatic calibration (fixed)
KCO2 -W
with automatic calibration (can be deactivated via DIP switches)
Multi-range switching (selectable via DIP switches)
0...2000 ppm; 0...5000 ppm
KCO2 - SD
0 -10 V (fixed)
KCO2 - W
0 -10 V or 4...20 mA, working resistance < 800 Ω
(selectable via DIP switches), with offset potentiometer (± 10 % of the measuring range)
KCO2 - SD
without changeover contact
KCO2 - W
with potential-free changeover contact (24 V / 1 A), switchpoint adjustable
typically ± 30 ppm ± 3 % of measured value
± 5 ppm ⁄ °C or ± 0.5 % of measured value ⁄ °C (whichever is higher)
± 0.13 % ⁄ mm Hg
< 2 % in 15 years
by diffusion
approx. 1 hour
–10...+60 °C
approx. 1 minute, minimum flow rate 0.3 m / s (air)
2
0.14 - 1.5 mm
, via screw terminals
plastic, UV-resistant, material polyamide, 30 % glass-globe reinforced, 
colour traffic white (similar to RAL 9016), housing cover for display is transparent!
KCO2 - SD
with snap-on lid,
KCO2 -W
with quick-locking screws (slotted ⁄ Phillips head combination)
72 x 64 x 37.8 mm (Tyr 1/Tyr 01 without display)
72 x 64 x 43.3 mm (Tyr 1 with display)
cable gland, plastic (M 16 x 1.5; with strain relief,
exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
TM
PLEUROFORM
, material polyamide (PA6), with torsion protection,
Ø 20 mm, NL = 202.5 mm, v
max
via flange made of plastic (included in scope of delivery)
III (according to EN 60 730)
KCO2 - SD
IP 54 (according to EN 60 529)* Housing tested,
TÜV SÜD, Report No. 713160960A (Tyr 01)
KCO2 - W
IP 65 (according to EN 60 529)* Housing tested,
TÜV SÜD, Report No. 713139052 (Tyr 1)
*Housing in the built-in state (permeable PLEUROFORM: IP 30)
CE conformity, electromagnetic compatibility according to EN 61 326, EMC Directive 2014 ⁄ 30 ⁄ EU
Display with illumination, two line, cutout approx. 36 x15 mm (W x H),
for displaying the Actual CO2 content and for setting the switchpoint
= 30 m/s (air)