Herunterladen Inhalt Inhalt Diese Seite drucken

Connecting The K-Bus Communication Interface (X2) - Koch PxtRX Betriebsanleitung

Aktives energiemanagement-gerät
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

5.2.3
Connectable
conductors:

Connecting the K-Bus communication interface (X2)

The K-Bus communication interface is used to exchange data between the devices of
the PxtRX active energy management device.
• Rigid conductor cross-section: 0.2 mm²...1.5 mm².
• Flexible conductor cross-section: 0.2 mm²...1.5 mm².
• Conductor cross-section according to AWG: 24...16.
• Flexible conductor cross-section with wire end ferrule without plastic sleeve:
0.25 mm²...1.5 mm².
• Flexible conductor cross-section with wire end ferrule with plastic sleeve:
0.25 mm²...0.75 mm².
• Mandrel gauge a × b / diameter: 2.4 mm × 1.5 mm / Ø 1.6 mm.
• Stripping length: 10 mm.
Fig. 12: Connector X2
Pin Signal
Description
K_V+
External power supply (option)
2
K_H
K-Bus signal (dominant high)
3
K_SHLD
Screen (option)
4
K_L
K-Bus signal (dominant low)
5
GND
Earth (of pin 1)
Operating manual PxtRX active energy management device
5 Commissioning
23
V1.1DE/EN