5 Commissioning
Connecting several
PxtRX and
storage units
(DLCM, battery)
22
Operating manual PxtRX active energy management device
V1.1DE/EN
2
+ -
Fig. 11: Storage connection diagram (2)
1
Application
2
storage unit (DLCM, battery)
Risk of damage!
Always connect each PxtRX active energy management device
via a two-pole fuse to the storage unit (DLCM, battery).
Mount the fuse as close as possible to the storage unit.
For parallel connection of several PxtRX devices with a common storage unit:
• The neutral point is the connecting terminal of the storage unit.
• Use a separate two-pole fuse for each PxtRX device.
• Use identical cabling for all PxtRX devices
(length, cross-section, routing, cable type).
Make sure that the storage unit (DLCM, battery) is compatible with the maximum
storage voltage set in the PxtRX.
Make sure that the storage unit (DLCM) is discharged or that the storage unit
(battery) is enabled.
Connect the negative pole to the storage unit (DLCM, battery) via a fuse with the
negative pole of the active energy management device (X5, pin 2).
Connect the positive terminal of the storage unit (DLCM, battery) to the positive
terminal of the active energy management device (X5, pin 1).
Twist single wires.
μC
DC+
~
3 ~
DC-
=
3
3
PxtRX active energy management device
1
=
M
3 ~
~
+
-
DRIVE
+
-
STORAGE