Herunterladen Inhalt Inhalt Diese Seite drucken

ABB ACQ580-34 Schnellinstallationsanleitung Seite 98

Vorschau ausblenden Andere Handbücher für ACQ580-34:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 23
98 Technical data and references
ACQ580
-34-...
U
= 400 V, 480 V (IEC)
n
246A-4
2 × (3 × 70 + 35)
293A-4
2 × (3 × 95 + 50)
365A-4
2 × (3 × 120 + 70)
442A-4
2 × (3 × 150 + 70)
EN
505A-4
3 × (3 × 95 + 50)
585A-4
3 × (3 × 120 + 70)
DA
650A-4
3 × (3 × 150 + 70)
U
= 480 V, UL (NEC)
n
DE
240A-4
2 × (3 × 70 + 35)
302A-4
2 × (3 × 95 + 50)
ES
361A-4
2 × (3 × 120 + 70)
414A-4
2 × (3 × 150 + 70)
FI
477A-4
3 × (3 × 95 + 50)
1) The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one
on top of the other, ambient temperature 30 °C (86 °F) PVC insulation, surface temperature 70 °C (158 °F) (EN
FR
60204-1 and IEC 60364-5-52). For other conditions, dimension the cables according to local safety
regulations, appropriate input voltage and the load current of the drive.
2) The cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire insulation at 40 °C
IT
(104 °F) ambient temperature. Not more than three current-carrying conductors in raceway or cable or earth
(directly buried). For other conditions, dimension the cables according to local safety regulations, appropriate
input voltage and the load current of the drive.
NL
Terminal and entry data for the power cables
PL
Maximum accepted cable
size
PT
Screw size for connecting
busbars to the drive mod ule
input and output busbars
RU
Tightening torque
SV
Overvoltage category
TR
(IEC/EN 60664-1)
Protective class (IEC/EN
61800-5-1)
ZH
Typical power cable sizes
1)
IEC
Cu cable type
2
mm
4 × (3 × 240) mm2 or 4 × (3 × 500 AWG)
M12
50...75 N·m (37...55 lbf·ft)
III
I
Al cable type
2
mm
2 × (3 × 95)
2 × (3 × 150)
2 × (3 × 185)
2 × (3 × 240)
3 × (3 × 150)
2 × 500 MCM or 3 × 250 MCM
3 × (3 × 185)
2 × 600 MCM or 3 × 300 MCM
3 × (3 × 240)
2 × 700 MCM or 3 × 350 MCM
2 × (3 × 95)
2 × (3 × 150)
2 × (3 × 185)
2 × (3 × 240)
3 × (3 × 150)
2 × 500 MCM or 3 × 250 MCM
2)
UL (NEC)
Cu cable type
AWG/kcmil
2 × 2/0
2 × 3/0
2 × 250 MCM
2 × 400 MCM
2 × 2/0
2 × 4/0
2 × 250 MCM
2 × 350 MCM

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Acs880-34

Inhaltsverzeichnis