Herunterladen Inhalt Inhalt Diese Seite drucken

Swegon LUNAd MB Bedienungsanleitung Seite 22

Inhaltsverzeichnis

Werbung

LUNAd MB
Register name Reg. no. Function
40039
38
40040
39
40041
40
40042
41
40043
42
40044
43
40045
44
40046
45
40047
46
40048
47
40049
48
40050
49
40051
50
40052
51
40053
52
22
Konstruktionsänderungen vorbehalten.
Description
Period time for A2
The ModBus value changes the selected period time for
at pulse output
the A2 output pulse. 5-995 = 0,5-99,5 minutes.
Runtime for
The ModBus value changes the selected total runtime
increase/ de-
for increase/decrease actuator in even 2-second
crease actuator
intervals
Valve exercise on
The ModBus value changes the selected day interval for
output D1
valve exercise on output D1. 0=Exercise off.
Valve exercise on
The ModBus value changes the selected day interval for
output D2
valve exercise on output D2. 0=Exercise off.
Valve exercise on
The ModBus value changes the selected day interval for
output A1
valve exercise on output A1. 0=Exercise off.
Valve exercise on
The ModBus value changes the selected day interval for
output A2
valve exercise on output A2. 0=Exercise off.
Not in use
Not in use, reserved for future use
Not in use
Not in use, reserved for future use
Not in use
Not in use, reserved for future use
Not in use
Not in use, reserved for future use
Not in use
Not in use, reserved for future use
Not in use
Not in use, reserved for future use
Not in use
Not in use, reserved for future use
Occupancy, on
Occupancy, on delay in minutes. Default = 0
delay
Occupancy, off
Occupancy, off delay in minutes. Default = 60
delay
20210408
Min
Max
Unit
5
99
min
20
510
sec.
0
30
days
0
30
days
0
30
days
0
30
days
0
255
min
0
255
min

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis