Herunterladen Inhalt Inhalt Diese Seite drucken
Inhaltsverzeichnis

Werbung

6.6.3 Bereich 3x

16-Bit-Statusregister (lesen)
Befehl 04 (Eingaberegister auslesen) zum Lesen.
Register name Reg. No.
30001
0
30002
1
30003
2
30004
3
30005
4
30006
5
30007
6
30008
7
30009
8
30010
9
30011
10
30012
11
30013
12
30014
13
30015
14
30016
15
30017
16
30018
17
Function
Regulated room temperature
External temperature sensor
Measured condensation volt
Desired room temperature
Current operation mode
Heating effect
Cooling effect
Effect to output D1
Effect to output D2
Effect to output A1
Effect to output A2
Voltage output, output A1
Voltage output, output A2
Program no. 1 (two last numbers)
Program no. 1 (two first numbers) 0-99
Version number
Drawing no. 1 (two last numbers)
Drawing no. 2 (two first numbers) 0-99
Description
0 - 319 = 0 - 31,9°C in stages of 0,1°.
0 - 319 = 0 - 31,9°C in stages of 0,1°.
0 - 255 = 0 - 5,1V in stages of 0,02V.
2,0 - 30,0°C in stages of 0,1 degree steps (20 - 300)
1 = DAY, 2 = NIGHT, 3 = SAVE.
The room controllers current heating effect in %.
The room controllers current cooling effect in %.
The room controllers current effect to output D1 in %.
The room controllers current effect to output D2 in %.
The room controllers current effect to output A1 in %.
The room controllers current effect to output A2 in %.
0-110 = 0-11,0 Volts
0-110 = 0-11,0 Volts
0-99
0-99
0-99
20210408
Konstruktionsänderungen vorbehalten.
LUNAd MB
Unit
°C
°C
°C
%
%
%
%
%
%
V
V
19