Herunterladen Inhalt Inhalt Diese Seite drucken

Swegon LUNAd MB Bedienungsanleitung Seite 21

Inhaltsverzeichnis

Werbung

Register name Reg. no. Function
40017
16
40018
17
40019
18
40020
19
40021
20
40022
21
40023
22
40024
23
40025
24
40026
25
40027
26
40028
27
40029
28
40030
29
40031
30
40032
31
40033
32
40034
33
40035
34
40036
35
40037
36
40038
37
Description
The ModBus value replaces the selected dead band value
for the DAY operation mode. Value 5-300 = 0,5 - 30°K in
1/2°-stages.
Dead band for the
The ModBus value replaces the selected dead band value
NIGHT operation
for the NIGHT operation mode. Value 5-300 = 0,5 - 30°K
mode
in 1/2°-stages.
Dead band for the
The ModBus value replaces the selected dead band value
SAVE operation
for the SAVE operation mode. Value 5-300 = 0,5 - 30°K in
mode
1/2°-stages.
The ModBus value replaces the selected P-range value
P-range for heating
for heating. Value 5-995 = 0,5 - 99,5°K in 1/2°-stages.
The ModBus value replaces the selected P-range value
P-range for cooling
for cooling. Value 5-995 = 0,5 - 99,5°K in 1/2°-stages.
The ModBus value replaces the selected I-time for
I-time for heating
heating. Value 0-995 = 0-99,5 minutes in 1/2-min.stages.
The ModBus value replaces the selected I-time for
I-time for cooling
cooling. Value 0-995 = 0-99,5 minutes in 1/2-min.stages.
Lowest limit of the
The ModBus value changes the selected lowest limit
con- trol range,
value for the effect range for output D1, "LIML %".
output D1
Lowest limit of the
The ModBus value changes the selected lowest limit
con- trol range,
value for the effect range for output D2, "LIML %".
output D2
Lowest limit of the
The ModBus value changes the selected lowest limit
con- trol range,
value for the effect range for output A1, "LIML %".
output A1
Lowest limit of the
The ModBus value changes the selected lowest limit
con- trol range,
value for the effect range for output A2, "LIML %".
output A2
Highest limit of the
The ModBus value changes the selected highest limit
con- trol range,
value for the effect range for output D1, "LIMH %".
output D1
Highest limit of the
The ModBus value changes the selected highest limit
con- trol range,
value for the effect range for output D2, "LIMH %".
output D2
Highest limit of the
The ModBus value changes the selected highest limit
con- trol range,
value for the effect range for output A1, "LIMH %".
output A1
Highest limit of the
con- trol range,
output A2
Minimum voltage
The ModBus value changes the selected minimum
for output A1
voltage level for output A1. 0-110 = 0,0-11,0 Volts
Maximum voltage
The ModBus value changes the selected maximum
for output A1
voltage level for output A1. 0-110 = 0,0-11,0 Volts
Minimum voltage
The ModBus value changes the selected minimum volt-
for output A2
age level for output A2. 0-110 = 0,0-11,0 Volts
Maximum voltage
The ModBus value changes the selected maximum volt-
for output A2
age level for output A2. 0-110 = 0,0-11,0 Volts
Period time for D1
The ModBus value changes the selected period time for
at pulse output
the D1 output pulse. 5-995 = 0,5-99,5 minutes
Period time for D2
The ModBus value changes the selected period time for
at pulse output
the D2 output pulse. 5-995 = 0,5-99,5 minutes
Period time for A1
The ModBus value changes the selected period time for
at pulse output
the A1 output pulse. 5-995 = 0,5-99,5 minutes
20210408
Konstruktionsänderungen vorbehalten.
LUNAd MB
Min
Max
Unit
5
300
°K
5
300
°K
5
300
°K
5
995
°K
5
995
°K
0
995
min.
0
995
min.
0
100
%
0
100
%
0
100
%
0
100
%
0
100
%
0
100
%
0
100
%
0
100
%
0
100
Volts
0
100
Volts
0
100
Volts
0
100
Volts
5
995
min
5
995
min
5
995
min
21

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis