Herunterladen Inhalt Inhalt Diese Seite drucken

Information Servicing - Carrier 42QTD009DS Serie Installationshandbuch

Vorschau ausblenden Andere Handbücher für 42QTD009DS Serie:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 21

7. INFORMATION SERVICING

7.1 CHECKS TO THE AREA
Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure
that the risk of ignition is minimised. For repair to the refrigerating system, the following precautions shall be
complied with prior to conducting work on the system.
7.2 WORK PROCEDURE
Works shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour
being present while the work is being performed.
7.3 GENERAL WORK AREA
All mintenance staff and others working in the local area shall be instructed on the nature of work being carried
out. work in confined spaces shall be avoided. The area around the work space shall be sectioned off. Ensure
that the conditions within the area have been made safe by control of flammable material.
7.4 CHECKING FOR PRESENCE OF REFRIGERANT
The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the
technician is aware of potentially flammable atmospheres. Ensure that the leak detection equipment being used
is suitable for use with flammable refrigerants, i.e. no sparking, adequately sealed or intrinsically safe.
7.5 PRESENCE OF FIRE EXTINGUISHER
If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire
extinguishing equipment shall be available to hand. Have a dry power or CO2 fire extinguisher adjacent to the
charging area.
7.6 NO IGNITION SOURCES
No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that
contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may
lead to the risk of fire or explosion. All possible ignition sources, including cigarette smoking, should be kept
sufficiently far away from the site of installation, repairing, removing and disposal, during which flammable
refrigerant can possibly be released to the surroungding space. Prior to work taking place, the area around the
equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks. "NO SMOKING"
signs shall be displayed.
7.7 VENTILATED AREA
Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conduct-
ing any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventila-
tion should safely disperse any released refrigerant and preferably expel it externally into the atmosphere.
7.8 CHECKS TO THE REFRIGERATION EQUIPMENT
Where electrical components are being changed, they shall be fit for the purpose and to the correct
specification. At all times the manufacturer's maintenance and service guidelines shall be followed. If in doubt
consult the manufacturer's technical department for assistance. The following checks shall be applied to
installations using flammable refrigerants:
7
GB-16

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis