Technical Data; Ordering Data - Siemens WZU-AM Bedienungsanleitung

Analogmodul

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Signal type 0...10 V or 0...20 mA, no overflow
Signal type 0...10 V or 0...20 mA, with overflow
Signal type 4...20 mA, no underflow, no overflow
Signal type 4...20 mA, with under-/overflow
© 2021 Siemens Switzerland Ltd.
Siemens Smart Infrastructure
10.

Technical Data

Power supply range
Power supply protection
<24 V
≥24 V
Max. current draw
Power consumption
Max. output load
Accuracy
Max. cable length
Wire cross section
11.

Ordering data

As accessory:
For meter with analog module:
For external power pack:
For 6-year D-cell:
A6V12324970_----_a
12 ... 30 V AC
12 ... 42 V DC
200 mA, slow blow
100 mA, slow blow
170 mV at 12 V
max. 2 W
300 Ω for current output, 2 kΩ for voltage output
(outputs are short-circuit proof)
≤ ± 1 % of parameterized maximum value
100 m
up to 1.5 mm²
WZU-AM
UH50-xxxx-xxxx-xxx-XYZx-xxx
UC50-xxxx-xxxx-xxx-XYZx-xxx
X = B
for battery-powered
X = M
for power supply AC/DC 24 V with plug
Y = A
for analog module in slot "module 1"
Z = A
for analog module in slot "module 2"
WZU-NE24 (for module: must always be ordered separate-
ly)
WZU-BD (for meter: if another battery type is fitted)