Herunterladen Inhalt Inhalt Diese Seite drucken

Safety Note - Benning PV 2 Bedienungsanleitung

Batteriebetriebener photovoltaiktester
Vorschau ausblenden Andere Handbücher für PV 2:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Protection class II
2.

Safety note

the notes and warnings given in these instructions at all times. Improper handling and non-
The connection to the PV generator is made exclusively in accordance with the
connection figure of the operating instructions.
Disconnect not required safety test leads from the BENNING PV 2.
The PV module/ PV string must not exceed the maximum opencircuit voltage
of 1000 V DC, the maximum short-circuit current of 15 A and the maximum DC
power (P = U x I) of 10 kW.
According to DIN EN 62446, the measurements have to be made for each PV
string.
Measuring at PV strings connected in parallel or contacting at the PV inverter
might involve damages of the BENNING PV 2!
The PV test sockets
PV generators (PV module, PV string).
Disconnect the BENNING PV 2 from the PV generator directly after the test.
Do not touch the measuring probes!
During insulating resistance measurements, high electric currents might be
applied to the measuring probes.
Do not touch any metal parts of the test object during measurement.
The PV generator must be isolated from the electric power supply!
Neither the positive nor the negative pole of the PV generator must be earthed!
12/ 2017
injuries or danger to life.
and
are intended exclusively for the connection with
17