CHAPTER 1:
RFE2500 SERIES SPECIFICATIONS:
1 Rated output voltage
2 Output voltage set point
3 Output voltage range
4 Rated Output Current at 180 ≤ Vin ≤ 265Vac (*1)
5 Rated Output Current at 170 ≤ Vin ≤ 180Vac (*1)
6 Rated Output Current at 100 ≤ Vin ≤ 132Vac (*1)
7 Rated Output Current at 85V ≤Vin < 100Vac (*1)
8 Rated output power at 180 ≤ Vin ≤ 265Vac
9 Rated output power at 170 ≤ Vin ≤ 180Vac
10 Rated output power 100 ≤ Vin ≤ 132Vac
11 Rated output power 85Vac ≤ Vin < 100Vac
12 Input voltage / frequency range
13 Maximum input current (at 115/230Vac)
14 Power Factor (Typ.) (at 115/230Vac)
15 Efficiency at 75% rated load (Typ.)
16 Efficiency at 100% rated load (Typ.)
17 Inrush current
18 Hold-up time
19 Maximum line regulation
20 Max load regulation
21 Output Ripple and noise P-P
22 Temperature stability
23 Temperature coefficient of output voltage
24 Remote sensing
25 Parallel operation
26 Series operation
27 Over current protection
85V ≤ Vin < 132Vac
170V ≤ Vin < 265Vac
28 Over voltage protection
29 Over temperature protection
30 Remote On/Off control
31 "DC OK" signal
32 Over-Temperature warning
33 "AC FAIL" signal
34 Auxiliary power supply output
35 Vout programming by external voltage
36 Vout programming by external resistor
37 OCP programming by external voltage
38 Rear panel indicators
39 I²C Interface
40 Operating temperature
41 Storage temperature
42 Operating humidity
43 Storage humidity
44 Cooling
45 Vibration
46 Shock
47 Conducted emission
48 Radiated emission
49 Immunity
50 Applicable safety standards
51 Withstand voltage
Input-Output:
Input-Ground:
Output - Ground:
52 Isolation resistance
53 Leakage current
54 Weight (Typ.)
55 Size (W*H*D)
RFE2500 & RFE2500/S (PMBUS) SERIES SPECIFICATIONS
V
V
V
A
A
A
A
Linear derating 1.3% per 1Vac from output current at 100Vac.
W
W
W
W
Linear derating 1.3% per 1Vac from output current at 100Vac.
(*2)
---
85~265Vac continuous, 47~63Hz, Single phase.
(*3)
A
15/12.
(*3)
---
>0.99/0.98 at maximum output power.
(*3)
%
(*3)
%
(*4)
A
Less than 50.
(*13)
mS
≥ 10mS typical at 115/230Vac input, rated output voltage and less than 80% of rated load.
(*5)
%
(*6)
%
(*7)
0~+70°C
mV
-10~0°C
mV
---
0.05% of rated Vout for 8hrs after 30min warm-up. Constant line, load and temp.
PPM/°C +/-200.
(*8)
---
Possible. Refer to Instruction Manual.
(*9)
---
Possible. Single wire current share, 5% accuracy of rated Iout, up to 8 units of the same voltage rating.
---
Possible (with external diodes), 2 units. Refer to Instruction Manual.
---
Minimum 105% of rated output current.
---
105~120% of rated output current.
(*10)
V
Tracking OVP, range: 1.1xVout, accuracy: +/-3%, refer to Instruction Manual.
---
Inverter shut down method, automatic recovery.
---
By electrical signal or dry contact. Refer to Instruction Manual.
(*14)
---
Tracking, On when Vout>90+/-5% of output voltage setting.
(*14)
---
Refer to Instruction Manual.
(*14)
---
On when 85Vac<Vin<270Vac.
(*3)(*11)
---
11.2~12.5V, 0.5A. 240mVp-p ripple and noise.
---
By 0~5V, equal to Vout min ~ Vout max. Refer to Instruction Manual.
---
By 1Kohm potentiometer. Refer to Instruction Manual.
---
By 0~5V. Refer to Instruction Manual.
---
DC OK. Refer to Instruction Manual.
---
Optional, PMBus compatible. Refer to Instruction Manual.
(*16)
---
-10~+50°C: 100% load.
+50°C to +60°C Derate 2%/°C of load.
+60°C to +70°C Derate 2.5%/°C of load.
---
-30~85°C.
---
10~90% RH, no condensation.
---
10~95% RH, no condensation.
---
By internal Fans. Variable speed control based on ambient temp and power level.
---
At no operation, 10-55Hz (Sweep for 1min.), 2G Constant X, Y, Z 1h each.
---
Less than 20G.
(*15)
---
Built to meet EN55032 Class B, FCC part 15 Class-B, VCCI Class-B.
(*15)
---
Built to meet EN55032 Class A, FCC part 15 Class-A, VCCI Class-A.
---
Built to meet IEC61000-4-2 (Level 2,3),
-3 (Level 2), -4 (Level 2), -5 (Level 3,4), -6 (Level 2), -8 (Level 4), -11
---
IEC 62368-1 UL62368-1 CSA22.2 No.62368-1 EN62368-1.
---
3000Vrms, 1min.
2000Vrms, 1min.
500Vrms, 1min.
---
More than 100Mohm at 25°C and 70% RH. Output-Ground: 500Vdc.
(*12)
mA
Less Than 0.8/1.6 at 115/230Vac range.
Kg
Max. 2.5.
---
107x41x320mm. Refer to Outline Drawing.
RFE2500-12
RFE2500-24
RFE2500-12/S
RFE2500-24/S
12
12+/-1%
9.6~13.2
19.2~29.0
200
200
125
2400
2400
1500
90/92
89/91
240
360
500Vrms, 1min.
1
RFE2500-48
RFE2500-48/S
24
24+/-1%
48+/-1%
38.4~58
96
96
62.5
31.25
2304
2496
2304
2400
1500
1500
90/92
91/93
89/91
90/92
0.25
0.50
240
360
2250Vdc, 1min.
48
52
50
480
780