Indications – Disturbance origins
Triggering of motor overheat protection (TK) can indicate
- wrong direction of rotation ( I ~ 2x I
- built up of dirt, hard running impeller and/or ball bearing failure
- too high air flow temperature
Abnormal noises can mean
- wrong direction of rotation
- worn out ball bearings
- bad vibration isolation to other buildings and ducting systems
Vibration can originate from
- unbalanced or dirty impellers
- insufficient vibration isolation from buildings and ducting systems
Extreme reductions in performance can occur
- with wrong direction of rotation
- if resistance to air stream through ducting and accessories (grilles, shutters, filters etc.) is higher than designed
c
Type
A
B
GBW 355/4 T120
500
500
150
GBD 355/4/4 T120 500
500
150
GBW 400/4.. T120
670
670
250
GBD 400/4/4 T120 670
670
250
GBW 450/4.. T120
670
670
250
GBD 450/4/4 T120 670
670
250
GBW 500/4 T120
670
670
250
GBD 500/4/4 T120 670
670
250
GBD 560/4/4 T120 800
800
250
GBD 630/4 T120
800
800
250
GBD 710/4 T120
1020 1020 250
SS-935
GBW.. T120
alternating
current,
1~ 230 V
TK in Reihe nur
mit Motor < 6A
L
85069 001 SS-935 24.03.09
SS-520
GBD 560/4/4 T120
rotary current,
3~ 400 V
32483 SS-520
)
n
fig.5
C
Ø D
E
F
355
30
30
355
30
30
400
30
30
400
30
30
450
30
30
450
30
30
500
30
30
500
30
30
560
30
30
630
30
30
710
30
30
U1-braun (BN)
U2-blau (BU)
Z1-schwarz (BK)
Z2-orange (OG)
TK-weiß (WH)
PE-gelb/grün (YE/GN)
N PE
5
Dimmensions in mm
TK TK