6.2.6
Adjusting limit values DA 12/14
Specify the limit value function of the relays.
Off
Switches off the limit value function of the relays.
working
The relay is energised if limit values are exceeded (energise-to-trip).
rest
Relay is de-energised when the limit value is exceeded (de-ener-
gise-to-trip).
Window
The relay is energised when the lower limit value is exceeded and
de-energised when the upper limit value is exceeded.
Tendency
The relay only switches in the case of a positive tendency of the signal.
Tendency
The relay only switches in the case of a positive tendency of the signal.
Sensor yyyyy
Detection of a probe error message (relay de-energises at le <3.8 mA).
- For this, the relay delay times must be set to >1 s.
o.SP (upper switching point)
The relay switches when the upper switching point is reached.
u.SP (lower switching point)
The relay switches when the lower switching point is reached.
Save
Confirm entries (yes) or reject (no).
- The changed relay is shown in the display and identified by a lower case
letter.
Delay (separate energise time/de-energise time)
The relay is switch on or off after a delay has expired (0 to
65536 seconds).
Next
The next relay is selected for adjustment.
Commissioning
DA 10/12/14
EN
24