Herunterladen Inhalt Inhalt Diese Seite drucken

AFRISO EURO-INDEX DA 10 Betriebsanleitung Seite 57

Digitales anzeigegerät
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

6.2.1
Setting analogue values
Set a measuring range.
Input manual
Adjust the measuring range (minimum value and maximum value).
- The unit and the adjustable range result from the selected input signal
(4 ... 20 mA, 10 V,...). If the product is to evaluate an input signal
between 4.5 ... 12.8 mA, the value 004.50 is set as minimum and the
value 012.80 as maximum.
Input learn
You can accept a measured value of a probe (for example when the tank
is completely full or empty).
1. Press the "set" key.
- The measured value is accepted as the minimum or maximum value.
6.2.2
Scaling
Assign a physical unit to a measured value.
Unit (scaling 1/2)
Select the required unit.
Position of decimal point/comma
Set the position of the decimal point.
Scaling
Set the value the product is to display at the start and the end of your
measurement.
Example:
Minimum: The input signal is 4 mA and Should display 000.00 litres.
Maximum: The input signal is 20 mA and Should display 500.00 litres.
Commissioning
DA 10/12/14
EN
22

Werbung

Inhaltsverzeichnis

Fehlerbehebung

loading

Diese Anleitung auch für:

Da 12Da 14

Inhaltsverzeichnis