11.8.5 Assigning and setting the alarm relay
Main menu > Setup
Submenu 1
Alarm relay
The following faults are output as alarm messages,
and the alarm relay switches automatically:
battery backup fault
open circuit current output.
If the alarm state is removed, the relay immediately
falls back automatically (no delay).
In addition, this submenu contains the following
settings for the alarm relay:
Selection of whether the alarm relay operates as
N.C. (fail safe) or N.O. contact
Confirmation of alarm messages.
In addition, for each sensor certain events can be
output to the alarm relay:
- exceeding of limit value 1
- exceeding of limit value 2
- fault during sensor test.
An alarm delay can be set in the relevant
Note
sensor menu in the main menu.
Submenu 2
Fail safe
Confirmation
Sensor 1
Sensor 2
Submenu 3
On (N.C.)
Off (N.O.)
Yes
No
Limit value 1 (S1)
Limit value 2 (S1)
Test sensor
Limit value 1 (S2)
Limit value 2 (S2)
Test sensor
Submenu 4
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
37