6.2.3 Special Circuitry
a) Circuitry for line fault detection if the contacts at the input are de-energised
Schematic
Create the circuitry for line fault detection in the immediate vicinity of the contact.
b) Circuitry with inductive loads at the output
Schematic
Connect inductive loads using a freewheeling diode.
Do NOT connect using a varistor.
7
Parameterization and Commissioning
DANGER! Explosion hazard from operating the DIP switches in Zone 2 while they are
live!
Non-compliance may result in serious or even fatal injury.
Adjust the DIP switches exclusively in a de-energised state.
Before commissioning, carry out the following checks:
• Mounting and installation of the device according to regulations.
• Correct, secure connection of the cables.
• No damage to the device or the cables.
• The screws are securely fastened to the terminals.
Correct tightening torque: 0.5 to 0.6 Nm.
Do not commission the device until it has been successfully tested.
7.1
Replacement of the Device
• If replacing this device with a device with an identical design, readjust the DIP switch if
necessary.
7.2
Parameterizations
DIP switch positions for line fault detection LF and inversion of the direction of action INV
Line fault detection LF
Deactivated/OFF *) Activated/ON
Chan-
OFF
ON
nel 1
1
Chan-
2
nel 2
*) Standard setting upon delivery
200089 / 9170612310
2020-04-30·BA00·III·en·09
1 k
10 k
15529E
+
-
15530E
OFF
ON
LF1
LF1
1
INV1
INV1
LF2
LF2
2
INV2
INV2
07456E
Parameterization and Commissioning
Short-circuit detection:
Open-circuit detection:
Direction of action inverted INV
Deactivated/OFF *)
OFF
ON
LF1
1
INV1
LF2
2
INV2
07455E
Switching repeater
Series 9170/.1
1 kO in series
10 kO parallel
Activated/ON
OFF
ON
LF1
1
INV1
LF2
2
INV2
15527E
15528E
11
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN