Herunterladen Inhalt Inhalt Diese Seite drucken

Stahl HART Serie Betriebsanleitung Seite 42

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Mounting and Installation
EN
8.2.2 Dismounting / Replacement of the Module
EN
• Loosen safety screws of the pluggable terminal X1.
EN
• Pull terminal from the module.
• If necessary, remove the partition.
EN
• Pull the blue notch lever of the module upwards to unlock the module.
EN
• Remove the module vertically from the BusRail.
EN
• Place the new module vertically onto the BusRail and press it lightly to snap it
into place.
EN
• The module may no longer be loosened without actuating the notch lever.
EN
• If necessary, snap the partition into place between the modules.
EN
• Plug the pluggable terminal X1 into the module and secure it against loosening using
screws (tightening torque 0.5 to 0.6 Nm).
EN
EN
Replacing modules
EN
EN
EN
EN
EN
EN
EN
EN
Observe the following when replacing an IS1 module with an IS1+ module with the
EN
same functions:
EN
• Ensure that the terminal assignment is adapted to that of the 9468/32.
• In order to use the new IS1+ functions, update the software of the CPM 9440 or
EN
CPU 9441 if necessary.
EN
• If necessary, use a new GSD in PROFIBUS-DP operation.
EN
• Please contact your responsible distributor for further information.
EN
18
HART Analog Universal Module
for Zone 1 / Div. 1
Series 9468/32
When replacing the module with a module with identical design, the set
parameters are maintained. No further user adjustments are necessary.
When replacing the module with a module with a different function,
the module reports a configuration error (red "ERR" LED flashes).
The module must be either re-configured or replaced with a module of
correct type.
218078 / 946860310010
2018-10-19·BA00·III·en·02

Werbung

Kapitel

Inhaltsverzeichnis

Fehlerbehebung

loading

Diese Anleitung auch für:

9468/32-08-11 aumh 08

Inhaltsverzeichnis