Adjustments
Calibration, Scrolling Method
4 mA calibration
20 mA calibration
7ML19985GD61
Downloaded from
www.Manualslib.com
There are several operating adjustments that can be made to The Probe.
• Press the "4" and "20" keys simultaneously until the desired adjustment is obtained. A viewing
sequence of the stored value is automatically initiated.
• During this time, press either the "4" or "20" key to change the value. After viewing or changing,
operation automatically reverts to the Run mode (6 sec).
4 mA calibration, scrolling
20 mA calibration, scrolling
blanking
speed of response
The 4 and 20 mA calibration values can be selected where reference levels, either from the material
in the vessel or from a target, cannot be provided. This method can also be used to trim the output
levels obtained by the Reference Method (see page 4).
• To change the stored calibration value, obtain the `c 4' or `c 20' display.
• Press the "20" key to increase or the "4" key to decrease the calibration value.
• After scrolling to the desired value, stop pressing the key. The display automatically reverts to the
Run mode (6 sec).
4 mA calibration initiated
view stored 4 mA calibration value i.e. 4.50 m
press"20" to increase to new calibration value i.e. 4.60 m
new calibration value
20 mA calibration initiated
view stored 20 mA calibration value
i.e. 0.50 m
press "4" to decrease to new calibration
value i.e. 0.45 m
new calibration value
The Probe – INSTRUCTION MANUAL
manuals search engine
alarm
fail-safe
fail-safe timer
units
For faster scrolling, hold the
Note:
key depressed during the
calibration adjustment and release
when desired value is obtained.