Connecting HART
Typical PLC/mA configuration with HART
Notes:
• Depending on the system
design, the power supply may
be separate from the PLC, or
integral to it.
• Loop resistance (total of cable
resistance plus 250 Ohm
[resistor]) must be less than
550 Ohm for the device to
function properly.
Wiring setups for hazardous area installations
1. Intrinsically Safe wiring
Device nameplate (ATEX/IECEX/INMETRO/C-TICK)
SITRANS LR260
7MLxxxx-xxxxx-xxxx-
Serial No: GYZ / S1034567
Encl.: NEMA / TYPE 4X, 6, IP67, IP68
Amb.Temp.: – 40°C to 80°C
Power Rating: 24 V
The ATEX certificate listed on the nameplate
can be downloaded from the product page of our website at: www.siemens.com/LR260. Go
to Support > Approvals / Certificates.
The IECEx certificate listed on the nameplate can be viewed on the IECEx website. Go to:
http://iecex.iec.ch and click on Ex Equipment Certificates of Conformity then enter the
certificate number IECEx SIR 11.0153X.
Device nameplate (FM/CSA)
FM/CSA Intrinsically Safe connection drawing number A5E03745229 can be downloaded
from the product page of our website at: www.siemens.com/LR260. Go to Support >
Installation Drawings > Level Measurement > Continuous - Radar.
• For power demands see
• For wiring requirements: follow local regulations.
• Approved dust-tight and water-tight conduit seals are required for outdoor NEMA 4X /
• Refer to
A5E32106122
Downloaded from
www.Manualslib.com
BOX 1
Nom., 30 V
Max., 4 - 20 mA
Siemens Milltronics Process Instruments, Peterborough
Assembled in Canada with domestic and imported parts
Loop Voltage versus Loop Resistance
type 4X / NEMA 6, IP67, IP68 locations.
Instructions specific to hazardous area installations
SITRANS LR260 (HART) – QUICK START MANUAL
manuals search engine
power
R= 250 
supply
SITRANS LR260
II 1 G D,
Ex ia IIC T4 Ga
Ex ta IIIC T100°C Da
SIRA 11ATEX2348X
IECEx SIR 11.0153x
HART
KCC-REM-S49
ARP0108 Ex ia IIC T4 Ga
SITRANSLR
WARNING: Use Cable Rated >100°C
ATENÇÃO - RISCO POTENCIAL DE CARGA ELETROSTÁTICA – VEJA INSTRUÇÕES
active PLC
HART modem
HART
communicator
1/2 D
, 2 D
Ui = 30 V
Ii = 120 mA
Pi = 0.8 W
OCP 0017
Ci = 15 nF
Ex ia IIC T4 Ga
Li = 0.1 mH
Ex ta IIIC T 100°C Da
DNV 12.0081 X
- UTILIZAR CABOS ADEQUADOS PARA TEMPERATURAS >100 °C
on page 19.
on page 9.
Page EN-7