1.3. Sensor Units
Selects the units for the Quick Start variables (high and
low calibration point, and level, distance, or space).
1.4. Operation
Operation
types
1.5. Low Calibration Point
Distance from Sensor Reference to Low Calibration Point: usually process empty level. See
Operation (1.4.) for an illustration.
Values
1.6. High Calibration Point
Distance from Sensor Reference to High Calibration Point: usually process full level. See
Operation (1.4.) for an illustration.
Values
Page EN-16
Downloaded from
www.Manualslib.com
sensor reference point
low cal.point
NO
The SITRANS LR260 stops updating measurements and associ-
SERVICE
ated loop current. Last valid measurement is displayed.
Distance to material surface referenced from Low Calibration
LEVEL
Point (process empty level).
Distance to material surface referenced from High Calibration
SPACE
Point (process full level).
Distance to material surface referenced from Sensor Reference
DISTANCE
Point.
Default: Distance
Range: 0.0000 to 30.000 m
Range: 0.0000 to 30.000 m
SITRANS LR260 (HART) – QUICK START MANUAL
manuals search engine
M, CM, MM, FT, IN
Options
Default: M
high cal.
point
distance
space
level
A5E32106122