IO-Link interface (continued)

6.5.12 Process data structure (PD Input Descriptor)

This parameter describes the composition of the process
data used.
Index
Subindex
PD Input
Descriptor
0
0x000E (14)
Tab. 6-17: Process data structure
6.6

Diagnostic data

The BMF 415KW-HAKKI-... reports diagnostic data
(events) to the controlling system (see Tab. 6-18) or the
controlling system can read out the status using the
diagnostics parameters.
6.6.1

Diagnostic parameters

Index
Subindex
0x0024 (36)
0
0x0025 (37)
0
0x0028 (40)
0
Tab. 6-18: Diagnostic parameters
6.6.2

Event list

Event code Expression Meaning
0x4210
Warning
0x4220
Warning
0x4000
Error
0x5000
Error
Tab. 6-19: Event list
18
english
Name
Size
Process data structure
3 bytes
Parameter
Size
Device Status
1 byte
Detailed Device Status 9 bytes
Process Data Input
1 byte
DEVICE TEMPERATURE OVERRUN (see section 6.5.6 Threshold values for the temperature
warning on page 16) – The set upper temperature threshold has been exceeded.
DEVICE TEMPERATURE UNDER-RUN (section 6.5.6 Threshold values for the temperature
warning on page 16) – The set lower temperature threshold has been exceeded.
TEMPERATURE FAULT- OVERLOAD – The temperature has exceeded the specified
maximum temperature. The heat source must be removed.
HARDWARE FAULT – There is a problem with the device hardware. Possible causes:
– Internal communication problem with the frontend
– Internal communication problem with the EEPROM
It may be that excessive electromagnetic interference is interrupting sensor-internal bus
communication. Communication resumes as soon as the interference is gone. If this is not the
case, the BMF 415KW-HAKKI-... must be replaced.
Access
Values
1 = Boolean set
2 = 2-bit length
Read Only
0 = 0-bit offset
Access
Values
Read Only
0 = Normal state
2 = Warning
4 = Error
Read Only
Up to 3 active events:
1st byte event type (0 = No event,
0xE4 = Warning, 0xF4 = Error)
2nd and 3rd byte event code (see sec. 6.6.2)
Read Only
Most recent valid process data (see sec. 6.2)