SELECTION OF PROGRAMMES AND FUNCTIONS WITH THE DIP-SWITCHES
DIP1 automatIC ClosIng
OFF = Activated
ON = Deactivated
DIP2 2 seConDs Pre-FlashIng
OFF = Activated
ON = Deactivated
DIP3 resPonse to rePeateD start CommanDs (8-9 terms.)
OFF = "Condominium" function: OPEN; only with the FCA in CLOSE;
in closing STOP and REOPEN
ON = only opening command (also select DIP1 OFF and/or DIP6 ON):
OPEN; in closing it stops and REOPENS.
Closing is only automatic after pause time (DIP1 OFF)
and/or after release of the photocell from FCA (DIP6 ON)

TRIMMER ADJUSTMENT

Working time: (Work)
Active only if DIP2 is OFF
Set a time of 4 to 8 seconds more than actual manoeuvre time.
With DIP2 ON, a maximum working time of 25 seconds (fixed) is selected.
Pause time: (Pause)
Active only if DIP1 is OFF
It allows adjustment from 4 to 110 seconds, starting from the FCA position.
When this time has elapsed a closing manoeuvre will start automatically.
Motor power: (Power)
When the initial inrush time of 2 seconds has finished it is easy to adjust the
electric power supplied to the motor.
N.B. Adjust with precision to limit the thrust force of the motorised barrier
according to the values established by current standards and such to guarantee
an adequate level of safety.
When installing and using these devices all the instructions provided by the manufacturer must be followed; the manufacturer will not be held responsible for any damages caused by improper or unreasonable use.
O&O s.r.l. declines all responsability for any inaccuracies contained in the following data sheet and reserves the right to modify the data at any time without prior notice.
REFERENCES ON THE CONTROL UNIT
ATTENTION! To memorise a new configuration, cut power off for a few seconds.
20
J8:
"Power" terminal board
J10: "Low voltage" terminal board (SELV)
21
K2:
Open relay
22
K1:
Close relay
K3:
Courtesy light relay
7
RX1: Radio receiver connector
8
U4:
BSX/BR model microprocessor
F1:
24 Vac (500 mA) fuse
9
F2:
12 Vac (500 mA) fuse
19
F3:
5A line fuse
J9:
Jump model BSX/BR card connector
30
S1:
Programming dip-switch
31
J5 e J6: Plugs for earth connections (line and motor).
32
14
15
44
230V
USER
DIP4 FunCtIonIng oF the FlashIng lIght outPut (11-12 terms.)
OFF = Flashing controlled directly by the control unit (use SL-LAMP model flashing light)
ON = Output always active with flashing controlled by the flashing light (SLR model)
DIP5 reVerser
OFF = Activated. In opening it STOPS and in closing it stops and reverses movement after knocking against an obstacle.
ON = Deactivated
DIP6 PhotoCell (8 - 19 terms.)
OFF = It acts only in closing, causing stopping and reopening.
ON = If released (NC returns) from the FCA position, it commands a closing manoeuvre.
During closing it carries out a safety function, stopping and reopening if interrupted.
Prior to powering on:
• Set the dip-switches according to the operation required.
• Check the electrical connections. Incorrect connections could damage the
equipment irreversibly.
Power on:
• Check that, under normal conditions, the LEDs relative to the N.C. inputs
are on.
• Check correct functioning of the START input, verifying that the LED only
turns on following a command.
• Check correct direction of movement (reversing, if necessary, the
connections on terminals 4 and 6) and limit switch connections (with the
bar at the end of its travel the corresponding LED should be off).
• Make sure the safety devices used are working properly.
• Carefully adjust the trimmers.
- 5 -
45
4
5
OPEN
COM
CLOSE
MOTOR 230 Vac
FINAL TEST