Transport, storage and packaging
3.1
General transport instructions
Check on delivery for completeness and transport damage.
Proceed as follows in the event of visible damage:
Do not accept delivery or only accept with reservations.
Record any transport damage on the transportation documents or on the transport company's
delivery note.
Submit a complaint to the freight forwarder.
IMPORTANT NOTE!
Warranty claims can only be made within the applicable period for complaints.
(More information is available in the T&Cs on the Kampmann website)
IMPORTANT NOTE!
2 people are needed to transport the unit. Wear personal protective clothing
when transporting the unit. Only lift the unit on both sides and not by the pipes /
valves.
IMPORTANT NOTE!
Material damage caused by incorrect transport!
Units being transported can drop or topple over if transported wrongly. This can
cause serious material damage.
Proceed carefully when unloading the equipment on delivery and when
transporting it on site and note the symbols and instructions on the pack-
aging.
Only use the holding points provided.
Only remove packaging shortly before assembling the unit
4
Installation and wiring
4.1
Requirements governing the installation site
Only install and assemble the unit if the following conditions are met:
Make sure that the wall/ceiling is sufficiently load-bearing to take the weight of the unit.
Make sure that the unit is securely suspended/standing.
Ensure that the airflow can circulate freely.
Provide adequate space for flow and return water connections on site.
There is a power supply on site.
If need be, provide a condensation connection with a sufficient gradient on site.
4.2
Minimum clearances
Air heaters can be installed free-standing or suspended on the wall using the supplied wall
brackets or suspended from the ceiling using the supplied ceiling brackets (Exception: Series 48
for ceiling mounting only). Installation using existing wall or ceiling brackets is likewise possible.
A minimum clearance L in accordance with the table below must be respected between unit suc-
tion area and wall/ceiling! If you do not leave this minimum clearance, the air heater output will
be reduced and the noise level will increase.
Be sure to observe the minimum clearances when using accessories or for maintenance pur-
poses!
L min
Minimum clearances TOP
Series
Type
44
44_58 / 44_56
45
45_58 / 45_56
46
46_58
47
47_58 / 47_56
48
48_68
* when using wall brackets, type 3_044
4.3
Installation
2 people are needed to install the unit.
CAUTION!
Risk of injury from sharp metal housing!
The inner metal of the casing can have sharp edges.
Wear suitable protective gloves.
IMPORTANT NOTE!
Horizontal installation of units!
When installing the units, ensure that they are completely horizontal to ensure
proper operation.
IMPORTANT NOTE!
Install connections in the de-energised state!
Connections must be installed without tension!
Use a suitable tool to protect terminal nuts from being sheared off and
twisted.
22
Assembly instructions
Minimum clearance L
Standard clearance L*
min.
160 mm
285 mm
180 mm
285 mm
230 mm
335 mm
300 mm
345 mm
620 mm
660 mm
TOP