Programming

The >SEI-Setup< programming software is required for programming the Serial essernet
interface type FACP 8000 / IQ8Control-Remote if the standard factory configuration needs to
be modified.
1
X12
Fig. 18: SEI1 Setup programming software
Serial essernet
Panel interface (Part No. 769828)
Service PC with >SEI Setup< programming software
DIP switch setting
To transmit the individually edited customer data via the programming software >SEI-Setup<
the following DIP switch setting is required.
ON
S2/1 – programming mode  ON / programming active
1 2
ON
S2/1 – programming mode  OFF / programming not active
1 2
ON
S2/2 – load default settings  ON (factory setting)
1 2
FB 798819 / 05.18
interface
Serial essernet
2
®
interface (SEI1)
3
63