Serial essernet
10.5

TWI-RS232 adapter (Part No. 583386.21)

®
The VARIODYN
D1 system can be connected to ESSER fire alarm systems via the TWI
interface using the TWI-RS232 adapter and the serial essernet
The TWI-RS232 adapter is used to transfer the TWI data to the RS232 protocol. The adapter is
connected to the DOM directly or via the supplied Cat5 cable.
1
X12
Fig. 17: Connection diagram TWI-RS232 adapter and SEI1
Serial essernet
RS232 cable
TWI-RS232 adapter (Part No. 583386.21)
DOM
11

Specifications - SEI1

Operating voltage
Current cunsumption
Ambient temperature
Storage temperature
Protection rating
Housing
Colour
Dimensions (W x H x D)
62
interface (SEI1)
2
3
2
3
5
®
interface (SEI1)
:
10.5 V DC to 28 V DC
:
approx. 60 mA @ 12 V DC
:
-5 °C to +50 °C
:
-10 °C to +50 °C
:
IP 31
:
ABS-plastic
:
white, similar to RAL 9003 / blue, similar to RAL 5003
:
270 x 221 x 71 (mm) incl. housing
®