Herunterladen Inhalt Inhalt Diese Seite drucken

Wiring Diagram - Helios KWL HB serie Montage- Und Betriebsvorschrift

Kwl-hygrobox
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Installation and Operating Instructions
EN

18. Wiring diagram

KWL Hygrobox KWL HB.. EH/WW
Connecting terminals 1 to 24 are la-
belled on the main board and designed
as relay outputs with 230 V (see figure).
With regard to the design with the water
heater battery, the 3-way motor mixer
valve and the circulation pump are con-
nected to the following relay outputs:
3-way motor mixer valve
(terminals 15 to 18):
Terminal 15 - phase mixer closed
Terminal 16 - phase mixer open
Terminal 17 - zero conductor
Terminal 18 - neutral conductor (earth)
Circulation pump (terminals 19 to 21):
Terminal 19 - phase
Terminal 20 - zero conductor
Terminal 21 - neutral conductor (earth)
The air humidification unit can be swit-
ched off (open contact) and on (closed
contact) in parallel with the ventila-
tion device with the ventilation unit
switch input. The switch input must be
33
activated in the Expert menu if auto-
matic synchronous operation cannot be
guaranteed because the sound level is
too low.
In the case of an external tempera-
ture sensor, a sensor can optionally
be connected, on the basis of which
the air outlet temperature is controlled
automatically. This is only required in
connection with a second heater battery
(low-temperature heater/air heater).
The floating output can be used for a
function check with an external regu-
lating and control unit for the possible
visualisation of faults.
E-heater batteries 1, 2, 3 and the fan
unit are only active in the electric ver-
sion.

Werbung

Kapitel

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Kwl hb 250 ehKwl hb 250 s wwKwl hb 500 s ww

Inhaltsverzeichnis