Helios KWL HB serie Montage- Und Betriebsvorschrift Seite 61

Kwl-hygrobox
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Installation and Operating Instructions
• In the following items, the relay outputs can be activated and deactivated manually.
Umwälzpumpe
Enthärterp.
Motor
Ventil
Ablauf Pumpe
E-
Heizung
1
E- Heizung
<
UVC-Check
Schwimmschalter<
. <
Zeit Vent.WaWe
Zeit Vent. Regl.
Laufzeit Misch.
Zeit Int. Misch.
Zeit Spülen
Betrieb UVC
KWL Hygrobox KWL HB.. EH/WW
Umwälzpump Ein<
<
Aus
Enthärterp.
Ein<
<
Aus
Motor
Ein<
<
Aus
<
Ventil
Ein<
Aus
AblaufPumpe Ein<
<
Aus
E-Heizung 1 Ein<
<
Aus
E- Heizung
Akt.
Deakt
UVC-Check
3,65
<
80%
Cal: 4,56
Schwimmschalter
>Ein
Aus
Zeit Vent. WaWe.
260s
Zeit Vent. Regl.
<
030s
Laufzeit Misch.
<
006s
Zeit int. Misch.
<
005min
Zeit Spülen
<
010min
Betrieb UVC
<
00001 h
Mischer Auf
<
Mischer Zu
<
Ventilator
<
UVC-Lampe
<
Hupe
<
• When E-heating Act. is set, the Open Mixer and Close
Mixer items are replaced by E-heating 2 and E-heating
.<
3.
• With the UVC Check parameter set, the current light out-
put of the UVC pipe is determined. At the top right, the
current value and the value calibrated is displayed un-
derneath that (light output of the new pipe). In compari-
son with the calibrated value, the light output is shown
as a percentage.
• This parameter is used to check the function of the floa-
ting switch. When the float is raised, the „>" character
changes from Off to On.
• The opening time for the water valve is set when the
water tank is filled (water level after water replacement).
Setting range: 20 – 600 seconds
Factory setting: 260 seconds KWL HB 250,
• This parameter is used to set the refill time of the water
during humidity control. The air humidity is determined
every minute. When the reference value is undershot, the
valve is opened according to a set value.
Setting range: 1 – 70 seconds
Factory setting: 30 seconds KWL HB 250,
• With this parameter, the runtime of the mixer can be set.
Setting range: 2 – 30 seconds
Factory setting: 6 seconds
• With the Time Interval Mixer parameter, the interval time
according to which the control system readjusts the mi-
xer can be set.
Setting range: 1 – 120 minutes
Factory setting: 5 minutes
• Defines the runtime of the rinsing programme.
Setting range: 1 – 20 minutes
Factory setting: 10 minutes
• Indicates the operating hours of the UVC pipe.
20
Mischer Auf
Ein<
Aus
Mischer Zu
Ein<
Aus
Ventilator
Ein<
Aus
UVC-Lampe
Ein<
Aus
Hupe
Ein<
Aus
180 seconds KWL HB 500