Helios KWL HB serie Montage- Und Betriebsvorschrift Seite 64

Kwl-hygrobox
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Installation and Operating Instructions
EN
Statusspeicher
AutoStby aktiv
Ext.Temp.Offset
Sprache
Luftf. max. 80%
Luftf. rel.
Temp.abs.Feuchte
Ext. Aus
Softwaretyp
KWL Hygrobox KWL HB.. EH/WW
AutoStby aktiv Ein
4
Aus<
Ext.Temp.Offset
+0.0
English
Deutsch<
Luftf. max.
Ein
Aus<
Luftf. rel.
Ein
Aus<
Temp.abs.Feuchte
21°C<
Ext. Aus
Ein
Aus<
250
<
500
23
• In the menu Status memory the last 9 actions of the
control unit can be retrieved with the time stored.
1) CHANGE WATER
2) DESCALE
3) FLUSH
4) UV_CHECK
5) STANDBY
6) CALIBRATE UV
7) CALIBRATE AIR
8) START
9) START USER
0) STANDARD
• The automatic deactivation of the air humidification unit
is deactivated with AutoStby active "Off". In addition,
number is now shown in the expert menu under "Au-
toStby active "On-Off" at the bottom on the left, which
shows the reason for the AutoStby operation:
1 – No ventilation for 18 hours
2 – EEPROM
3 – Valve openings
4 – Switch
5 – Rinsing
• The external temperature sensor can be calibrated here.
• The menu guidance can be switched over from German
to English or to French and vice versa in the menu opti-
on Language.
• If the parameter "Max. air humidity" is set to "On", the
air humidity setting in the customer menu is expanded
by the values 70 % and 80 %.
This parameter must not be activated in an air
duct system, if it is integrated into the air hu-
midification unit. (Condensation water may
form in the piping system!)
• In the menu "Relative air humidity" the humidity control
is switched from the absolute air humidity control at 21
°C to the relative air humidity control.
This parameter must not be activated in an air
duct system, if it is integrated into the air hu-
midification unit. (Condensation water may
form in the piping system!)
• The temperature is set here, to which the absolute hu-
midity control is related. The value can be set between
20°C and 24°C in 1-degree increments. This enables the
adjustment of the humidity control to the room tempe-
rature.
• When the parameter "External Off" is set to "On" and if
the contact is open at the external switching input, the
device is switched to the operating status "Control Off"
(For more details, see section 9.4) Air flow monitoring via
the integrated microphone will still remain active.
• Displays the parameterized device type. This setting can
only be adjusted in the factory defaults menu item.