3.4 ELECTRICAL WIRING

ATTENTION:
Do not swap neutral and phase over, follow the diagram shown carefully and carry out a good earth con-
nection.
The section of the conductors must be at least 1mm2. (Unless requested otherwise by local standards and legislation).
The electrical wiring carried out by the installer must be in compliance with the rules in force in the country.
~
50Hz 230V
PE L
N
Safety thermostat
7 pin plug
7 pole socket
D1913
Ignition
electrodes

CONTROL BOX

To remove the control-box from the burner, loosen screw (A, fig. 10)
and pull to the arrow direction, after removing all components, the
7 pin plug and earth wire.
In case of disassembly of the control box, retighten the screw
(A) with a torque wrench setting of 1 – 1.2 Nm.
Main switch
T6A
Limit thermostat
Brown
Blue
Black
White
Blue
Burner-earth
(See page 4). Connect the automatic shut-off
device (230V - 0.5A max.) to the clamps N - B4
of the 7 pin plug.
TESTING
Check the shut-down of the burner by opening
the thermostats and the lock-out by darkening
the photoresistance.
Hour counter
(230V - 0.1A max.)
Remote lock-out signal
(230V - 0.5A max.)
Photoresistance
Oil valve
Capacitor
Motor
5
GB
Fig. 10
S7072
A
1915