Herunterladen Inhalt Inhalt Diese Seite drucken

Installation Of The Indoor Unit - McQuay L -Serie Bedienungsanleitung

Inverter wall mounted split type air conditioner
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 33
Drain work.
(Heat Pump Unit Only)
1) Use drain plug for drainage.
2) If the drain port is covered by a mounting base or fl oor surface, place
additional foot bases of at least 30mm in height under the outdoor unit's
feet.
3) In cold areas, do not use a drain hose with the outdoor unit.
(Otherwise, drain water may freeze, impairing heating performance.)
The indoor unit must be installed in such a way so as to
prevent short circuit of the cool discharged air with the hot
return air. Please follow the installation clearance shown
in the fi gure. Do not place the indoor unit where there
could be direct sunlight shining on it. Also, this location
must be suitable for piping and drainage, and be away
from doors or windows.
Air fl ow
(Indoor)
min. 50
Required space
(Space for
maintenance)

INSTALLATION OF THE INDOOR UNIT

The refrigerant piping can be routed to the unit in a
number of ways (left or right from the back of the unit), by
using the cut-out holes on the casing of the unit.
Bend the pipes carefully to the required position in order
to align it with the holes. For the side and bottom out,
hold the bottom of the piping and then position it to the
required direction. The condensation drain hose can be
taped to the pipes.
min. 50
(Space for
maintenance)
All dimensions are in mm
1-6
Right-side, right-back or right-bottom piping
Right-side
piping
Remove pipe port cover
here for right-side piping
Right-bottom
piping
Remove pipe port cover
here for right-bottom piping
Left-side, left-back or left-bottom piping
Remove pipe port cover here for left-bottom
piping
Drain water hole
Bottom frame
Drain plug
Hose (available commercially,
inner dia. 16mm)
Right-back piping
Bind coolant pipe and
drain hose together
with insulating tape.
Remove pipe port cover
here for left-side piping
Left-side piping
Left-back piping
Left-bottom piping

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

M5lcy10/15fr

Inhaltsverzeichnis