Maintenance

SITRANS LR 200 requires no maintenance or cleaning under normal operating conditions. If
cleaning becomes necessary under severe operating conditions:
1.
Note the antenna material and the process medium, and select a cleaning solution
that will not react adversely with either.
2.
Remove the instrument from service and wipe the antenna clean using a cloth and
suitable cleaning solution.
Unit Repair and Excluded Liability
For detailed information, please see the inside back cover.
Instructions specific to hazardous area installations
(Reference European ATEX Directive 94/9/EC, Annex II, 1/0/6)
The following instructions apply to equipment covered by certificate number SIRA
03ATEX2142X:
1.
For use and assembly, refer to the main instructions.
2.
The equipment is certified for use as Category 1G equipment.
3.
The equipment may be used with flammable gases and vapors with apparatus
group IIC and temperature class T4.
The equipment is certified for use in an ambient temperature range of –40 °C to
4.
80 °C.
5.
The equipment has not been assessed as a safety related device (as referred to by
Directive 94/9/EC Annex II, clause 1.5).
6.
Installation and inspection of this equipment shall be carried out by suitably trained
personnel in accordance with the applicable code of practice (EN 60079-14 and
EN 60079-17 in Europe).
7.
Repair of this equipment shall be carried out by suitably trained personnel in
accordance with the applicable code of practice (e.g. EN 60079-19 within Europe).
8.
Components to be incorporated into or used as replacements in the equipment shall
be fitted by suitably trained personnel in accordance with the manufacturer's
documentation.
9.
It is the responsibility of the user to ensure that manual override is possible in order
to shut down the equipment and protective systems incorporated within automatic
7ML19985QG81
SITRANS LR 200 (PROFIBUS PA) – QUICK START MANUAL
Page EN-13