Routine maintenance

Control
General cleaning and checking unit
Finned coils
Fans
Compressor: oil check
Exchangers
General cleaning and checking unit
Every six months, the unit should be cleaned using a moist cloth.
Every six months it is also good practice to check the general conditions
of the unit. In particular, make sure there is no corrosion on the unit
structure. Any corrosion must be treated with protective paints in order
to prevent possible damage.
Cleaning of Finned Coils
DANGER!
Pay attention to the edges of the coil
The coils must be washed and brushed gently with water and soap.
Remove any foreign bodies from the condensing coils which may block
the passage of air, such as: leaves, paper, debris, etc.
Replace the coils should it not be possible to clean them.
Failure to clean the coils increases load losses and therefore reduces
To better protect the coils, we recommend assembly of the RPB (coil
Section II :: Installation and maintenance
Every 6 months, the unit must undergo general washing
and its status must be checked
Variable depending on where the unit is installed.
Variable depending on where the unit is installed.
Every 6 months
Every 12 months
Every 6 months
Notes
Any points where corrosion is starting need to be
touched up with protective paint.
The coils must be kept clear from any obstruc-
tions. If needed, they must be washed with
keep them from being damaged. Always use the
personal protective equipment foreseen by law
(goggles, earmuffs, etc.).
The fan grilles must be kept clear from any
obstructions.
The lubricating oil level in the compressor can be
checked by means of the sight-glass.
Any incrustation of the exchanger may be de-
tected by measuring the pressure-drop between
the inlet and outlet pipes, using a differential
pressure gauge.
ned from time to time.
Remove dry dust and dirt or normal soiling with:
- soft brush or hand broom
- compressed air (3 to 5 bar)
- industrial vacuum cleaner
- hosepipe (water, 3 to 5 bar)
Remove coarse or stubborn dirt with:
- high pressure cleaner (max pressure 50 bar; min. distance 400
mm; fan with nozzle)
- steam cleaner (max. pressure 50 bar; min. distance 400 mm;
fan with nozzle)
- Use neutral cleaning agent if necessary.
- Avoid aggressive or corrosive detergents in order to not affect
the aluminium or the rest of the unit.
-
gent on the condenser.
85
To guarantee free air circulation:
• clean the condenser regularly.
For economical and reliable operation:
• remove leaves, paper, dust, pollen,
etc. from the condenser.
Note
The frequency of the cleaning inter-
ventions depends on the installation
site.