4 Using the device

4.1 Settings

4.1.1 Reset

4.1.2 Test

Prior to initial commissioning, the rated motor current must be set on the
overload relay by means of the current dial (→ table 1, → table 2, page 33).
CAUTION
If the overload relay is installed at a cool location (e.g. -5 °C) and
the motor is installed at a warm motor installation site (e.g.
40 °C), it is possible that there will be a delayed release during
an overload if the devices are operated in the lower current
setting range.
The user can select automatic restart "A" or manual reset "H" on the
ZB-.../XTOB... overload relays by means of the Reset selector button.
H
A
Figure 14:Switching options of the Reset selector button
The factory set position "H" on the overload relay prevents automatic
restarts. In position "H", the relay must be reset manually after it has tripped
by pressing the selector button.
The ZB.../XTOB... overload relays are equipped with a Test button that has
an integral dual function.
OFF
TEST
Figure 15:Switching options of the Test button
The auxiliary contact 95-96 is opened by pulling the Test button, and can thus
be used to switch off the contactor relay.
The function of both auxiliary contacts can be tested in current-less state by
pulling the button.
ZB65-..., ZB150-... 11/17 MN03407005Z-DE/EN www.eaton.com
NO 97
NC 95
NO 98
NC 96